Data centre solutions

From chillerto chip.

Data centre solutions

From chillerto chip.

Prefabricated stainless steel piping for liquid-cooled halls. Headers, CDU spools, row manifolds and rack drops, made clean, tested and ready to bolt in.

1.9GW

India’s installed data centre capacity in FY26, up from about 0.8 GW in FY23.

7+GW

Expected by 2030, with roughly 4.5 GW more in the pipeline.

55%

Share of that capacity expected to run AI workloads by FY30. Those racks need liquid cooling.

Source: KPMG in India, July 2026, as summarised by eCorpIT.

Follow the coolant

Five stops.
One loop.

Tap any part of the loop, from the plant room to the rack, to see what we supply there and which grade goes where.

01PLANT02FWS HEADERS03CDU04ROW MANIFOLD05RACK DROPS
Supply, cool Return, warmTap any part of the loop
Facility side

The plant

Chillers, cooling towers or dry coolers reject the heat. Water or a water-glycol blend leaves the plant room on the facility loop.

What we supply here

  • Large-bore pipe
  • Flanges
  • Reducers and tees
  • Pump-skid spools
304
Alloy
18–20% Cr, 8–10.5% Ni
Why here
Good corrosion resistance at lower cost, for most distribution duty.
Try it

Size a row
in ten seconds.

Slide in your racks and heat load. See the coolant flow and the stainless pipe sizes it points to, then send it to us for a price.

Racks in the row12
Heat per rack80 kW
Supply to return ΔT10 K
Row heat load
960 kW
Coolant flow
1,378 L/min
82.7 m³/h
Row manifold
5" Sch 10S
1.62 m/s
Rack drops
1½" Sch 10S
1.33 m/s each

A first estimate, not a design. Water, 4.18 kJ/L·K, velocity kept at or under 2 m/s in the manifold and 1.5 m/s in drops. Glycol mixes need more flow. Your engineer of record sizes the real line.

Quote this row
Why prefabricate

Built in the shop.
Bolted on site.

Data halls are built on tight schedules, often next to live IT load. Shop-built spools take welding, testing and cleaning off the critical path.

No hot work on live floors

Welding happens in our shop. On site, your crew bolts spools together, away from running IT load.

Pressure tested before dispatch

Every spool is hydro tested and ships with its test record.

Clean inside, capped outside

Pickled, passivated, flushed and dried, then end-capped and bagged so nothing gets in on the way to site.

Traceable to the heat

Each spool tag links to its mill certificates, weld map and inspection report.

Polished 304/316L spools or headers in a clean bay.
Gauge or test certificate beside a stainless spool.
Spool ends capped and wrapped for clean delivery.
Building a liquid-cooled hall?

Send the P&IDs.
We’ll send spools.

Isometrics, a line list or a design brief. We’ll price it and plan deliveries around your build sequence.

Talk to an engineer